Infrared thermography – evaluation of the results reproducibility

Elton Bauer (Civil and Environmental Engineering Department, University of Brasilia, Faculty of Technology, Brasília, Brasil)
Vasco Peixoto de Freitas (Civil Engineering Department, Laboratory of Building Physics, University of Porto, Faculty of Engineering, Porto, Portugal)
Niubis Mustelier (Laboratory of Building Physics, University of Porto, Faculty of Engineering, Porto, Portugal)
Eva Barreira (Civil Engineering Department, Laboratory of Building Physics University of Porto, Faculty of Engineering, Porto, Portugal)
Sara Stingl de Freitas (Laboratory of Building Physics, University of Porto, Faculty of Engineering, Porto, Portugal)

Structural Survey

ISSN: 0263-080X

Article publication date: 13 April 2015

544

Abstract

Purpose

Infrared thermography is increasingly being used to diagnose pathologies in buildings, such as façade defects. The purpose of this paper is to assess the results reproducibility and the equipment influence on the measurements. To do so, it was defined as case study the assessment of rendering delamination.

Design/methodology/approach

Two infrared cameras of different makers were used to detect the presence of defects deliberately created in specimens. The tests were done in the laboratory with a heat source. The defects were detected through a temperature gradient between the zones with and without defect.

Findings

With this thermographic imaging, it was possible to identify the defects in the specimen both qualitatively and quantitatively. The results were found to be reproducible in the three cycles performed. The influence of the equipment on the results was of little significance for the quantitative assessment criterion “temperature difference between zones with and without defect”, but for the criterion “absolute surface temperature”, the difference in the results yielded by the two cameras was around 1.8°C.

Originality/value

The results suggest that there is reproducibility of the measurements, considering both the qualitative and quantitative approach, when assessing delamination, irrespective of the maker of the equipment used. The influence of the equipment on the results depends on the quantitative assessment criterion used.

Keywords

Citation

Bauer, E., de Freitas, V.P., Mustelier, N., Barreira, E. and de Freitas, S.S. (2015), "Infrared thermography – evaluation of the results reproducibility", Structural Survey, Vol. 33 No. 1, pp. 20-35. https://doi.org/10.1108/SS-05-2014-0021

Publisher

:

Emerald Group Publishing Limited

Copyright © 2015, Emerald Group Publishing Limited